Strona 1 - INSTALLATION MANUAL

Models: MULTI18HP230V1COMULTI24HP230V1COMULTI30HP230V1COMULTI36HP230V1COMULTI42HP230V1CODUCTLESS INVERTER HEAT PUMPINSTALLATION MANUAL

Strona 2 - Table of Contents

TERRA INDOOR UNIT INSTALLATIONModel ABCTERRA09HP230V1AH34.1 (866) 11.5 (292) 8.2 (208) TERRA12HP230V1AH34.1 (866) 11.5 (292) 8.2 (208) TERR

Strona 3 - SAFETY PRECAUTIONS

TERRA INDOOR UNIT INSTALLATIONTerra Unit Mounting Bracket Diagrams (inches)9K and 12K Unit18K Unit24K UnitLeft Right(Rear piping hole) (Rear piping ho

Strona 4 - NOMENCLATURE

VIREO INDOOR UNIT INSTALLATIONBCA11Model ABCVIR09HP230V1B 33.4(848) 11.4 (290)8.2 (208)VIR12HP230V1B 33.4(848) 11.4 (290)8.2 (208)VIR18HP230V1B

Strona 5 - SYSTEM REQUIREMENTS

Vireo Unit Mounting Bracket Diagrams (inches)VIREO INDOOR UNIT INSTALLATION9K and 12K Unit18K Unit24K Unit4.621.47.34277.38.1 276.03.17.41.41.41.57.5

Strona 6 - SUGGESTED TOOLS

Piping Design and LayoutThe piping design and layout are critical factors for the overall performance and reliability of the system. Find the desired

Strona 7 - Indoor Unit

Piping Length Requirements The system piping layout must take in the constraints of horizontal length on system performance. The outdoor unit has a le

Strona 8

Piping Height Requirements The system piping layout must take in the constraints of vertical height on system performance. The outdoor unit has a vert

Strona 9

OUTDOOR UNIT INSTALLATION18K Unit24K UnitOutdoor Unit Dimensions1635.138.022.035.122.013.417.338.613.415.627.631.114.514.5

Strona 10 - PIPE SIZE – in(mm)

OUTDOOR UNIT INSTALLATION30K Unit36K and 42K UnitOutdoor Unit Dimensions1736.214.617.338.424.040.014.343.417.314.842.524.831.015.7

Strona 11 - 24K Unit

Install Ground Pad or Wall Hangers1. Determine proper location for outdoor unit.2. Follow all instructions provided by manufacturer for installing w

Strona 12

Table of ContentsSafety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Nomenclature . .

Strona 13

INDOOR UNIT INSTALLATION Install Mounting Bracket1. Attach the mounting bracket to the indoor unit. 2. Find the horizontal center of the indoor unit

Strona 14 - INDOOR UNIT INSTALLATION

Carefully cut hole in the side of the front panel for piping to enter indoor unit as shown below. Find and mark the proper location for the wall hole

Strona 15

Refrigerant PipingPIPING INSTALLATION Use refrigeration grade piping ONLY. Uses of other piping will void the Manufacturer’s Warranty.CAUTION21Piping

Strona 16

PIPING INSTALLATION 4.Properly align piping and tighten flare nut using a standard wrench and a torque wrench as shown in figure to the below. Careful

Strona 17 - OUTDOOR UNIT INSTALLATION

How to Relocate Drain Hose from Left to Right Side (if required)1. Locate drain plug on right side of the drain tray. Firmly grab it and remove from d

Strona 18

Indoor Drain PipingThe indoor wall unit uses a gravity drain system. There is no internal condensate pump. The drainhose must slope downward with no k

Strona 19

Piping Connections to Outdoor Unit1. Remove service valve cover (if provided) to accessthe service valves and refrigerant ports. The outdoorunit refr

Strona 20

PIPING INSTALLATION 3. Apply a small amount of refrigerant oil to the flare connection on the refrigerant pipe. 4. Properly align piping and tighten

Strona 21

POWER AND WIRING INSTALLATION To the power supplyTo unit BPower cordTo unit Aconnecting cableL1L2P connecting cablec cableT

Strona 22 - PIPING INSTALLATION

POWER AND WIRING INSTALLATION L1L2To the power supplyL1 L2LCCDC cableT cableT cablePower cordL1L2 To unit AConn

Strona 23

SAFETY PRECAUTIONSPlease read the following before installation.This is the safety alert symbol. It is used to alert you to potential personal injury

Strona 24

POWER AND WIRING INSTALLATION High Wall Indoor Wire ConnectionDisconnect all electrical power to indoor and outdoor units including disconnects, fuses

Strona 25

Outdoor Unit Wire Connections Disconnect all electrical power to unit including disconnects, fuses and breakers. 1. Remove the service panel on right

Strona 26

POWER AND WIRING INSTALLATION Setting Master-Slave Indoor Units (24K Size Only)Typically, the outdoor unit will select a master indoor unit upon power

Strona 27

Leaking TestLeak test each indoor unit, one unit at a time. Repeat the leak test sequence for each indoor unit.1. Connect the charging hose of the ma

Strona 28

Using Vacuum Pump(con’t):5. Evacuate using either deep vacuum or triple evacuation method.6. After evacuation is complete, fully close the low side

Strona 29 - Electrical Diagrams

START-UP34Start-up Checklist□Turn on main power to all indoor and outdoor units.• Verify the system is not displaying an error code on the indoor unit

Strona 30 - Connections

35TROUBLESHOOTINGPROBLEMSystem does not restart.Indoor unit emits unpleasant odorwhen startedYou hear a“water flowing”sound.A thin fog or vapor coming

Strona 31 - Mounting Panel

TROUBLESHOOTINGPROBLEMWater leaking from the indoor unit into the room.Wireless remote controller does not work.The unit will not deliver air.Moisture

Strona 32

37DIAGNOSTIC CODESX-fan ModeIndoor Evap Coil Temperature Sensor MalfunctionGas valve temperature sensoris open/short circuitedSystem ConfigurationMalf

Strona 33 - TESTING AND INSPECTION

38Indoor UnitDisplayOutdoor Unit IndicatorsMalfunction Name Possible CausesDIAGNOSTIC CODESHigh TemperatureResistant ProtectionCold Air ProtectionEEPR

Strona 34

Outdoor UnitNOMENCLATURE3

Strona 35 - START-UP

39Indoor UnitDisplayOutdoor Unit IndicatorsMalfunction Name Possible CausesDIAGNOSTIC CODESIndoor Coil Freeze Protection - Frequency Decrease/Limit Mo

Strona 36 - TROUBLESHOOTING

Notes: 1) During defrosting process, the heating indicator is on for 10s and off for 0.5s.2) Refer to Service Manual for additional information.Ind

Strona 37

Outdoor Model Size2-Zone 3-Zone 4-Zone 5-ZoneAPPENDIX AAuthorized Indoor Unit Combinations419+99+129+99+129+18 12+1212+18 18+189+99+129+18 9+24 12+121

Strona 38 - DIAGNOSTIC CODES

LIMITED WARRANTY STATEMENTFOR WARRANTY SERVICE OR REPAIR:Contact your installing contractor. You may find the installer’s name on the equipment or in

Strona 39

SYSTEM REQUIREMENTSREFRIGERANT CHARGEELECTRICAL REQUIREMENTS Notes: 1) System must be on a single dedicated circuit.2) Main power is supplied to the

Strona 40

• Standard Wrench• Adjustable/Crescent Wrench• Torque Wrench• Hex Keys or Allen Wrenches• Drill & Drill Bits• Hole Saw• Pipe Cutter • Scre

Strona 41

INSTALLATION SITE INSTRUCTIONSIndoor UnitSelect a site that allows for the following:1. Ensure the installation complies with the installation minimu

Strona 42 - APPENDIX A

Air inletAir outlet20 in (0.5 m)20 in (0.5 m)39 in (1.0m)20 in (0.5 m)78 in (2.0 m)1. Install the outdoor unit at a location that is capable of wit

Strona 43 - LIMITED WARRANTY STATEMENT

PIPE SIZE – in(mm)Unit Size (BtuH) Liquid Line Suction/Gas Line9,000 1/4 (6) 1/2 (12)12,000 1/4 (6) 1/2 (12)18,000 1/4 (6) 5/8 (16)CROWN INDOOR UNIT I